REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
3-69
HEST 905 028 C
0
5
10
15
I
i
14.14
N
10 I
t
0
t
N
Setting current
Output signal
Fig. 3.5.4.1 Operation of the peak value overcurrent function
Typical settings:
a) Peak value phase fault protection
I-Setting according to application
Delay 0.01 s
f-min 40 Hz
b) Phase fault protection of a machine with synchronous starter
during start-up
I-Setting 1.5 I
N
Delay 5 s
f-min 2 Hz