ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-86
D. Directional overcurrent settings - DirCurrentDT
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet4..1 P1
(
Select
)
Trip B00000000
CurrentInp CT/VT-Addr 0
VoltageInp CT/VT-Addr 0
I-Setting IN 2.0 0.1 20.0 0.01
Angle Deg 45 -180 +180 15
Delay s 1.00 0.02 60.00 0.01
tWait s 0.20 0.02 20.00 0.01
MemDirMode Trip (Select)
MemDuration s 2.00 0.20 60.00 0.01
Receive BinaryAddr T
Ext Block BinaryAddr F
Trip SignalAddr ER
Start SignalAddr
Start R SignalAddr ER
Start S SignalAddr ER
Start T SignalAddr ER
MeasFwd SignalAddr
MeasBwd SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the function’s
tripping output (matrix tripping logic).
CurrentInp
defines the c.t. input channel. Only three-phase c.t’s can be
set and the first channel (R phase) of the group of three
selected must be specified.
VoltageInp
defines the v.t. input channel. Only three-phase v.t’s can be
set and the first channel (R phase) of the group of three
selected must be specified.