ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-118
D. Definite time voltage function settings - Voltage-DT
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Delay s 02.00 0.02 60.00 0.01
V-Setting UN 1.200 0.010 2.000 0.002
MaxMin MAX (1ph) (Select)
NrOfPhases 001 1 3 1
VoltageInp AnalogAddr 0
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
Delay
time delay between pick-up and tripping.
V-Setting
Voltage setting for tripping.
MaxMin
defines operation as overvoltage or undervoltage. Settings:
· MIN (3ph): undervoltage
Monitors highest phase voltage in the three-
phase mode
· MIN (1ph): undervoltage
Monitors lowest phase voltage in the three-
phase mode