ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-140
D. Peak value voltage function settings - Voltage-Inst
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Delay s 00.01 0.00 60.00 0.01
V-Setting UN 1.40 0.01 2.00 0.01
f-min Hz 40 25 50 1
MaxMin MAX (Select)
NrOfPhases 001 1 3 2
VoltageInp CT/VT-Addr 0
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix).
Delay
Time between the function picking up and tripping.
V-Setting
Pick-up voltage setting.
f-min
defines the minimum frequency for which measurement is
required.
MaxMin
defines operation as overvoltage or undervoltage. Settings:
· MAX: overvoltage
· MIN: undervoltage.
NrOfPhases
defines whether single or three-phase measurement.