ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-210
Typical settings:
V/f-Setting 1.1 VB/f
N
VB-Setting according to protected unit
t-min 0.2 min
t-max 60 min
t [V/f = 1.05...1.50] according to protected unit
1)
t-Reset according to protected unit
1)
Refer to Fig. 3.5.21.1 for typical settings for a Westinghouse unit.