ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-212
D. Balanced voltage function settings - Voltage-Bal
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (selectable)
Trip 00000000
V-Unbalance UN 0.20 0.10 0.50 0.05
Delay s 0.04 0.00 1.00 0.01
t-Reset s 1.50 0.10 2.00 0.01
NrOfPhases s 003 1 3 2
VoltInpLine1 AnalogAddr 00000
VoltInpLine2 AnalogAddr 00000
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Trip-Line1 SignalAddr
Trip-Line2 SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
V-Unbalance
Voltage difference setting for tripping.
Difference between the amplitudes of the two voltage input
channels which results in tripping. The setting applies to all
three phases in the three-phase mode.
Delay
time delay between pick-up and tripping.
t-Reset
Time required for the measurement to reset after the tripping
condition has disappeared (reset ratio: 0.90).