ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-254
AdjRErInp
switches the protection function to the REr determination
mode.
(F
® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
AdjCoupCInp
switches the protection function to the C determination mode.
(F
® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
BlockInp
Binary address used as blocking input.
(F
® FALSE, T ® TRUE, binary input or output of a protec-
tion function).
Trip
Output for signalling tripping.
StartTrip
Output for signalling the pick-up of the tripping stage.
Alarm
Output for signalling alarm.
StartAlarm
Output for signalling the pick-up of the alarm stage.
InterruptInt
Output for signalling an open-circuit injection circuit.
InterruptExt.
Output for signalling an open-circuit measuring circuit.
Output for signalling an open-circuit injection circuit. Both
pick-up and reset of this signal are delayed by 5s.
REr-Adjust
Output for signalling the binary status of ‘AdjRErInp'.
CoupC-Adjust
Output for signalling the binary status of ‘AdjCoupCInp'.
Extern-Block
Output for signalling that the function is disabled by an exter-
nal signal.