ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-320
D. Counter settings - Count
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Count-Thresh 1 1 100 1
Drop-Time s 00.04 00.01 30.00 00.01
Reset delay s 010.0 000.1 300.0 000.1
BinaryInp BinaryAddr F
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix tripping logic).
Count-Thresh
Number of input impulses counted by the counter before it
trips.
Drop time
Time the counter output signal is maintained after the input
signal causing it has reset.
Reset-Delay
Time after the input signal has reset before the counter is
reset to zero if it did not trip.
BinaryInp
Counter input
xx: - all binary inputs (or outputs of protection
functions).