ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-334
D. Voltage plausibility function settings - Check-U3ph
Summary of parameters:
Text Units Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
V-Setting UN 0.20 0.05 1.20 0.1
Delay s 10.0 0.1 60.0 0.1
VT-Compens 01.00 -2.00 +2.00 0.01
VoltageInp CT/VT-Addr 0
SumInp CT/VT-Addr 0
BlockInp BinaryAddr F
Trip Signaladdr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
Definition of the tripping logic (matrix) excited by the
function's output.
V-Setting
Voltage setting for tripping.
Delay
Time between start signal at the I/P and the tripping signal at
the O/P.
Forbidden setting:
£ 1 s for voltage settings £ 0.2 U
N
.
VT-Compens
Amplitude compensation factor for the residual voltage I/P,
enabling different transformation ratios of the main v.t's for
phase and residual voltages to be equalised.
The polarity of the residual voltage can be reversed by enter-
ing negative values.