ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
5-102
5.12.8. SRIO settings
Refer to ‘Programming manual SRIO 1000M and 500M’ having
the No. ‘34 SRIO 1000M 2 EN1 B’ for how to program the SRIO
500/1000M.
SRIO 500/1000M must be configured as follows:
BUS_MODE:
BUS Code MODE
1 9 Saco 100M Slave mode
2 6 Fast SPA Master mode
3 0 Null mode
4 10 Terminal mode
BUS-Setup:
setup BUS 1 BUS 2 BUS 4
baud 9600 9600 9600
parity 2 2 0
stopbit 1 1 1
cts100
dcd100
aut.lf 1 0 1
timeout 60000 3000 0
resend 0 3 0
ANSI_SETUP must be set to ‘half-duplex’; the other parameters
in ANSI_SETUP are of no consequence.
After the new BUS modes have been saved (STORE F), the
system has to be restarted.
The SRIO slave address must agree with the address in the file
re-01.cfg (950). The SRIO address is set in SYSPAR P4.
A (dummy) data point must be entered in the SRIO data base for
every device in the SPA-BUS loop.