ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. C
6-12
MVB information
Note that the information is continuously refreshed.
MVB-IBB-DiagInfo:
Working Mode: InterbayBus
PC-Card Status: Ready
PC-Card Error: No Error
PC-Card Type: InterbayBus
PC-Card SW-Vers: 1.11 1997-12-15
PC-Card HeartBeat: 55384
Driver State: Ready
Driver Heartbeat: 4877
Nr. of received Messages: 12
Nr. of transmitted Messages: 12
Nr. of Transmission Fails: 0
Nr. of lost incoming Messages: 0
Fig. 6.7 MVB information
The table below explains the significance of the various items of
information.
Working mode Indicates the function of the PC card as connection
to the inter-bay bus. If a PC card is not inserted, “Not
connected” is displayed on this line.
PC-Card Status Initialising, Ready, Minor error, Fatal error
PC-Card Error No error, Unknown error, No response, Init. Error,
Subsystem error etc.
PC-Card Type Inter-bay bus. If a PC card is not inserted, “Software
unknown” is displayed.
PC-Card SW-Vers. PC card firmware date and version
PC-Card Heartbeat Signals whether the PC card firmware is active or not.
Driver State Initialising, Ready, Minor error, Fatal error
Driver Heartbeat Signals whether the driver software in the RE.316*4
is active or not.
No. of received
messages
Total number of messages received since the
information was deleted.
No. of transmitted
messages
Total number of messages received since the
information was deleted.