REG 316*4 1MRB520049-Uen / Rev. C ABB Switzerland Ltd
7-27
Caution:
If a processor board, type 316VC61b is replaced in a unit,
check the jumpers according to Fig. 7.9. These jumpers are
located between the two connectors.
Including LDU: X2200 – X2201
X2203 – X2204
X2206 – X2207
Excluding LDU: X2201 – X2202
X2204 – X2205
X2207 – X2208
Fig. 7.9 Jumper positions on the 316VC61b processor board
for devices including and excluding a local control
and display unit (LDU) on the front
(derived from HESG 324 526)