REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-13
9.6. SPA address list
9.6.1. Channel 0
Summary of parameters:
Address Access Text Default Step
V102 R VC type identification 316VC61
V104 R VC software version
V110 R, W Master event mask 1 Q events
masked
0 Bit mask active
2 All events masked
V115 R Time telegram counter
V116 R Date telegram counter
V120 R Restart counter 0
V200 R, W SPA address 2 2...255
V201 R, W Baud rate 9600 4800, 9600, 19200
F R Module Type REC316 REG316, REL316,
RET316
S0 R Number of functions 0 1...60
S1 R Function type number S1...S60
S100 R, W Parameter set switch 1 1...4
TR, WTime
D R, W Date and time
L R Read event
B R Read event again
Date format: YY-MM-DD hh.mm;ss.sss