REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-15
9.6.5. Channel 4 event list
Event No Cause Event mask Enable code
4E21 PC-Card No failure V156 16
4E22 PC-Card Fatal error V156 32
4E23 PC-Card Non-urgent error V156 64
4E24 PC-Card Not ready V156 128
9.6.6. Channel 4 analogue input
Channel 4 provides 64 data points which are available either for
analogue FUPLA inputs or analogue outputs via the distributed
input/output unit 500AXM11. The numerical range is
-32768...+32767 (16 Bit integers).
The data can be entered in decimal or 4-digit hexadecimal for-
mat.
The data remains intact in the event of a supply failure.
Real values are converted to integers,
integer=real ´ 100.
Input format: nnn.mm.
FFFFH
Data point number: O1...O64
9.6.7. Binary input signals
The significance of the events, for standard as well as for double
signals, is explained in Section 9.6.14.
Channel Inputs Events Slot
101 I1 - I16 E1 - E32 1
102 I1 - I16 E1 - E32 2
103 I1 - I16 E1 - E32 3
104 I1 - I16 E1 - E32 4