ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-26
9.6.18. Current-DT 2
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R Delay s 00.01 0.00 60.00 0.01
14S10 R I-Setting IN 04.00 0.1 20 0.1
14S11 R f-min Hz 040.0 2 50 1
14S12 R MaxMin <Select> MAX -1 1 2
MIN -1
MAX 1
14S13 R NrOfPhases 001 1 3 2
Measured variables
Address Access Text Dec.
14V1 R IN 2
Tripping levels
Address Access Text Dec.
14Q1 R IN 2
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8