ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-30
Address Access Text Unit Default Min. Max. Step
14S20 R InrushRatio % 10 6 20 1
14S21 R InrushTime s 5 0 90 1
Measured variables
Address Access Text Dec. Address Access Text Dec.
14V1 R IN (Id-R) 2 14V4 R IN (IhR) 2
14V2 R IN (Id-S) 2 14V5 R IN (IhR) 2
14V3 R IN (Id-T) 2 14V6 R IN (IhR) 2
Tripping levels
Address Access Text Dec.
14Q1 R IN (Id-R) 2
14Q2 R IN (Id-S) 2
14Q3 R IN (Id-T) 2
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Trip-R Set V155 4 14I2
14E4 Ditto Reset V155 8
14E5 Trip-S Set V155 16 14I3
14E6 Ditto Reset V155 32
14E7 Trip-T Set V155 64 14I4
14E8 Ditto Reset V155 128
14E9 Inrush Set V155 256 14I5
14E10 Ditto Reset V155 512
14E11 Stabil Set V155 1024 14I6
14E12 Ditto Reset V155 2048

Table of Contents