REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-39
9.6.29. Power 18
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R P-Setting PN -0.050 -0.100 1.200 0.005
14S10 R Angle deg 000.0 -180.0 180.0 5.0
14S11 R Drop-Ratio % 60 30 170 1
14S12 R Delay s 00.50 0.05 60.00 0.01
14S13 R MaxMin <Select> MIN -1 +1 2
MIN -1
MAX 1
14S14 R Phi-Comp. deg 0.0 -5.0 5.0 0.1
14S15 R NrOfPhases 001 1 3 1
14S16 R PN UN*IN 1.000 0.500 2.500 0.001
Measured variables
Address Access Text Dec.
14V1 R PN 3
Tripping levels
Address Access Text Dec.
14Q1 R PN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8

Table of Contents