Loading...
REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-53
9.6.34. Frequency 25
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R Frequency Hz 48.00 40.00 65.00 0.01
14S10 R U-Block UN 0.20 0.20 0.80 0.10
14S11 R Delay s 01.00 0.10 60.00 0.01
14S12 R MaxMin <Select> MIN -1 1 2
MIN -1
MAX 1
Measured variables
Address Access Text Dec.
14V1 R Hz 3
14V2 R UN 2
Tripping levels
Address Access Text Dec.
14Q1 R Hz 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Block.(U<) Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Trip Set V155 4 14I2
14E4 Ditto Reset V155 8
14E5 Start Set V155 16 1I3
14E6 Ditto Reset V155 32

Table of Contents