9.6.37. Overtemp. (RE. 316*4) 28
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R
Theta-Beginn
% 100 000 100 001
14S10 R Theta-Warn % 105 050 200 001
14S11 R Theta-Trip % 110 050 200 001
14S12 R NrOfPhases 1 1 3 2
14S13 R
TimeConstant
min 005.0 002.0 500.0 000.1
14S14 R IB-Setting IN 1.00 0.50 2.50 0.01
Measured variables
Address Access Text Dec.
14V1 R Theta-Nom 3
14V2 R Pv-Nom 3
14V3 R IN 3
Tripping levels
Address Access Text Dec.
14Q1 R Theta-Nom 3
14Q2 R Pv-Nom 3
14Q3 R IN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Alarm Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Trip Set V155 4 14I2
14E4 Ditto Reset V155 8