ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-58
9.6.39. Check-U3ph 30
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R U-Setting UN 0.20 0.05 1.20 0.05
14S10 R Delay s 10.0 0.1 60.0 0.1
14S11 R
VT-Compens
+1.00 -2.00 +2.00 0.01
Measured variables
Address Access Text Dec.
14V1 R UN 3
Tripping levels
Address Access Text Dec.
14Q1 R UN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2