REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-73
9.6.48. SynchroCheck 49
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R maxVoltDif UN 0.20 0.05 0.40 0.05
14S10 R maxPhaseDif deg 10.0 05.0 80.0 05.0
14S11 R maxFreqDif Hz 0.20 0.05 0.40 0.05
14S12 R minVoltage UN 0.70 0.60 1.00 0.05
14S13 R maxVoltage UN 0.30 0.10 1.00 0.05
14S14 R Operat.-Mode <Select> SynChck only 0 4 1
SynChck only 0
DBus + LLine 1
LBus + DLine 2
DBus ½ DLine
3
DBus + DLine 4
14S15 R SupervisTime s 0.20 0.05 5.00 0.05
14S16 R t-Reset s 0.05 0.00 1.00 0.05
14S17 R LiveBus <Select> 1ph R-S 0 7 1
1ph R-S 0
1ph S-T 1
1ph T-R 2
1ph R-E 3
1ph S-E 4
1ph T-E 5
3ph-delta 6
3ph-Y 7