ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-76
9.6.49. Rotor-EFP 51
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R Alarm-Delay s 0.50 0.20 60.00 0.05
14S10 R Trip-Delay s 0.50 0.20 60.00 0.05
14S11 R
RFr-AlarmVal
kOhm 10.0 0.1 25.0 0.1
14S12 R RFr-TripVal kOhm 01.0 0.1 25.0 0.1
14S13 R REr kOhm 1.00 0.90 5.00 0.01
14S14 R Uir <Select> 50 Volt 1 3 1
20 Volt 1
30 Volt 2
50 Volt 3
14S15 R RFr-Adjust kOhm 10.00 8.00 12.00 0.01
14S16 R
CoupC-Adjust
uF 4.00 2.00 10.00 0.01
Measured variables
Address Access Text Dec.
14V1 R Rfr (kOhm) 1
14V2 R Ck" (uF) 2
14V3 R REr" (kOhm) 2
Tripping levels
Address Access Text Dec.
14Q1 R Rfr (kOhm) 1
14Q2 R Ck" (uF) 2
14Q3 R REr" (kOhm) 2