REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-83
9.6.53. Diff-Line 56
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R g IN 0.20 0.10 0.50 0.10
14S10 R v 0.50 0.25 0.50 0.25
14S11 R b 1 1.50 1.25 5.00 0.25
14S12 R g-High IN 2.00 0.50 2.50 0.25
14S13 R I-Inst IN 10 3 15 1
14S14 R a1 1.00 0.05 2.20 0.01
14S15 R s1 <Select> D 0 1 1
Y0
D1
14S16 R a2 1.00 0.05 2.20 0.01
14S17 R s2 <Select> d0 00 21 1
y0 0
y1 1
y5 2
y6 3
y7 4
y11 5
d0 6
d1 7
d5 8
d6 9
d7 10
d11 11

Table of Contents