REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-103
9.6.61. df/dt 69
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R df/dt Hz/s -1.0 -10.0 10.0 0.1
14S10 R Frequency Hz 48.00 00.00 65.00 0.01
14S11 R BlockVoltage UN 0.2 0.2 0.8 0.1
14S12 R Delay s 00.10 0.10 60.00 0.01
Measured variables
Address Access Text Dec.
14V1 R Hz/s 2
14V2 R Hz 3
14V3 R UN 2
Tripping levels
Address Access Text Dec.
14Q1 R Hz/s 2
4Q2 R Hz 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Blocked(U<) Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 TRIP Set V155 4 14I2
14E4 Ditto Reset V155 8