ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-108
9.6.64. BreakerFailure 72
Basisc channel No.: 14
Summery of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R 23105 TRIP t1 00000000B
14S9 R 23110 TRIP t1 L1 00000000B
14S13 R 23115 TRIP t1 L2 00000000B
14S17 R 23120 TRIP t1 L3 00000000B
14S21 R 23125 TRIP t2 00000000B
14S25 R 23130 REMOTE TRIP 00000000B
14S29 R 23135 RED TRIP L1 00000000B
14S33 R 23140 RED TRIP L2 00000000B
14S37 R 23145 RED TRIP L3 00000000B
14S41 R 23150 EFS REM TRIP 00000000B
14S45 R 23155 EFS BUS TRIP 00000000B
14S49 R
I Setting
IN 1.20 0.2 5 0.01
14S50 R
Delay t1
s 0.15 0.02 60 0.01
14S51 R
Delay t2
s 0.15 0.02 60 0.01
14S52 R
Delay tEFP
s 0.04 0.02 60 0.01
14S53 R
t
Drop Retrip
s 0.05 0.02 60 0.01
14S54 R
t
Drop BuTrip
s 0.05 0.02 60 0.01
14S55 R
t
Pulse RemTrip
s 0.05 0.02 60 0.01
14S56 R t1 active <Select> on 0 1 1
off 0
on 1
14S57 R t2 active <Select> on 0 1 1
off 0
on 1
14S58 R RemTrip active
<Select>
on011
off 0
on 1