ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-54
D. Generator differential function settings - Diff-Gen
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 000000
g-Setting IN 0.10 0.10 0.50 0.05
v-Setting 0.25 0.25 0.50 0.25
CurrentInp AnalogAddr 0
BlockInp BinaryAddr F
Trip SignalAddr ER
Trip-R SignalAddr
Trip-S SignalAddr
Trip-T SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the Tripping channel activated by the tripping output
of the function (tripping logic).
g-Setting
Basic setting (sensitivity) g of the operating characteristic.
v-Setting
Pick-up ratio (slope) of the operating characteristic.
CurrentInp
defines the A/D input channels. The first channel (R phase)
of the two groups of three phases must be specified.
BlockInp
Binary address used as blocking input.
F: - Not blocked
T: - Blocked
xx: - all binary inputs (or outputs of a protection
function).