Insert either offline or online IED
Import a template IED that is available in the template library as a .pcmt file
Import a preconfigured IED available as a .pcmi file
PCM600 uses two kinds of IED files: .pcmt and .pcmi. Both files include
the complete IED configuration but their usage differs. The .pcmt files are
always accessed through the PCM600 template manager while the .pcmi
files are meant for sharing the IED instances between different PCM600
users enabling quick import/export directly from the plant structure
context menu.
IEC 61850 Edition 1 and Edition 2 IEDs cannot be used simultaneously in
the same PCM600 project. The first inserted IED determines the IEC
61850 version for the whole project.
From the plant structure, it is possible to see whether the inserted IED is in the offline or
online mode. A red cross in front of the IED symbol indicates offline mode, a green tick
indicates online mode.
GUID-F9E16EA2-CDE7-4488-8CC5-5B66849C89FC V1 EN
Figure 21: Plant structure showing Bay1 in the online mode and Bay2 in the offline
mode
Section 4 1MAC108982-MB E
Setting up a project
48 615 series ANSI
Engineering Manual