4.3.1 Inserting an IED in online mode
To set up an IED online, the protection relay must be connected to PCM600.
When the protection relay is already connected to PCM600, PCM600 can read the order
number directly from the relay. It is possible to read the full configuration from the relay
by using the Read from IED function.
1. In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Motor Protection IEDs and select the protection relay type
to be inserted.
Alternatively, drag an IED from the Object Types view to the bay
level.
GUID-AF88B4EA-85AF-43E8-AED7-D6EF9DD25B9C-ANSI V1 EN
Figure 22: Selecting the protection relay type
2. On the Configuration mode selection page, select Online Configuration and click
Next.