ABB Relion 615 series - Inserting an IED in Offline Mode

ABB Relion 615 series
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data cannot be scanned from the protection relay and proceeding is
prevented if the IED is not online or if the IP address is not correct.
4.3.2 Inserting an IED in offline mode
When the protection relay is not available or is not connected to PCM600, engineering can
be done offline. The offline configuration in PCM600 can be written to the protection
relay later when it is connected.
Working in the offline mode has an advantage compared to online mode in that the
preparation for the configuration can be started even though the protection relay is not
available.
1. In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Feeder IEDs and select the protection relay type to be
inserted.
Alternatively, drag an IED from the Object Types view to the bay
level.
2. On the Configuration mode selection page, select Offline Configuration and click
Next.
Setting up an IED in the offline mode is similar as in the online mode; however, with
the offline mode it is not necessary to type the correct IP address in the
Communication port and IP address dialog box.
Section 4 1MAC108982-MB E
Setting up a project
58 615 series ANSI
Engineering Manual