BIO
BIO
RTD
FBs
Binary
Inputs
Binary
Outputs
Analog
Inputs
Hardware
IO interfaces
Signal Matrix
FBs
IEC 61850
GOOSERSV
(input side)
GOOSE
FBs
FBs
GOOSERSV
(output side)
Functions
FBs
FBs
GUID-50BC48B0-574F-4DD8-9678-67A0954D1C13 V1 EN
Figure 57: Signal Matrix: operation principles
A binary input channel can be connected to one or more function block inputs. If a binary
input channel is connected to several different function blocks in the Application
Configuration tool, the connection appears as glue logic in Signal Matrix.
A binary output channel can only be activated from one function block output. If it is
activated from more than one function block output, the glue logic has to be used.
Section 5 1MAC108982-MB E
Protection and control engineering
90 615 series ANSI
Engineering Manual