EasyManua.ls Logo

ABB RET670 - Phase-To-Ground Faults; Phase-To-Phase Faults

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.4.3.1 Phase-to-phase faults
ZAngPP
ZPP
1
23
Ohm/phase
R
X
IEC07000009-4-en.vsd
50%
IEC07000009 V4 EN
Figure 27: Proposed test points for phase-to-phase fault
Table 22: Test points for phase-to-phase (ohms / phase)
Test
points
reach Value Comments
1 X ZPP · sin(ZAngPP)
R ZPP · sin(ZAngPP)
2 X 0,5· (ZPP· sin(ZAngPP)
R 0,5·ZPP + ΔR = 0,5·ZPP·(1+cos(ZAngPP))
3 X 0,5·ZPP·sin(ZAngPP)
R 0,5·ZPP - ΔR = 0,5·ZPP(1-cos(ZAngPP))
Change the magnitude and angle of phase-to-phase voltage to achieve impedances at test
points 1, 2 and 3. For each test point, observe that the output signals, PICKUP, PU_x and
PHPH_FLT are activated where x refers to the actual phase to be tested. After the timer
tPP for the actual zone has elapsed, also the signals TRIP, TRPP and TR_x shall be
activated.
11.4.3.2 Phase-to-ground faults
For simplicity, the same test points as for phase-to-phase faults are proposed, but
considering new impedance values.
Section 11 1MRK 504 165-UUS -
Testing functionality by secondary injection
122 Transformer protection RET670 2.2 ANSI
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Related product manuals