EasyManuals Logo

ABB RET670 Commissioning Manual

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #129 background imageLoading...
Page #129 background image
ZAngPG
50%
Ohm/loop
R
X
ANSI07000010-1-en.vsd
ANSI07000010 V1 EN
Figure 28: Proposed test points for phase-to-ground faults
Table 23: Test points for phase-to-ground loops A-B (Ohm/Loop)
Test
points
Reach Value Comments
1 X ZPG · sin(ZAngPG)
R ZPG · cos(ZAngPG)
2 X 0,5·ZPG · sin(ZAngPG)
R 0,5·ZPG + ΔR = 0,5·ZPG · (1 - cos(ZAngPG))
3 X 0,5·ZPG·sin(ZangPG)
R 0,5·ZPG - ΔR = 0,5·ZPG · (1 - cos(ZAngPG))
Check also in the same way as for phase-to-ground fault for each test point that the output
signals PHG_FLT, are activated where x refers to the actual phase to be tested. After the
timer tPG for the zone has elapsed, also the signals TRIP, TRPG and TR_x shall be
activated.
11.4.4 Faulty phase identification with load encroachment FMPSPDIS
(21)
There is no specific test routine for this function. The function is tested in conjunction with
other impedance (mho) functions.
1MRK 504 165-UUS - Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI 123
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals