11.4.9 Power swing detection ZMRPSB (68)
The aim is to verify that the settings of the Power swing detection function ZMRPSB (68)
is according to the setting table and to verify that ZMRPSB (68) operates as expected.
Prepare the IED for verification of settings outlined in Section
"Preparing the IED to
verify settings".
Before starting this process, all impedance measuring zones shall be set and in operation.
Test the outer resistive boarder in forward and reverse direction, RLdOutFw and
RLdOutRv and the inner reactive boarder in forward and reverse direction X1InFw and
X1InRv. See figure 37.
The corresponding resistive border for the inner resistive boundary and outer resistive
boundary is calculated automatically from the setting of kLdRFw and kLdRRv.
The inner zone of ZMRPSB (68) must cover all zones by at least 10% margin.
The test is mainly divided into two parts, one which aim is to verify that the settings are
in accordance to the selectivity plan and a second part to verify the operation of ZMRPSB
(68). The proposed test points for validation of the settings are numbered according to
figure
37
Test of the interactions or combinations that are not configured are not considered in this
instruction.
Section 11 1MRK 504 165-UUS -
Testing functionality by secondary injection
142 Transformer protection RET670 2.2 ANSI
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals