11.8.1.3 Overcurrent feature with voltage restraint
Procedure
1. Connect the test set for injection of three-phase currents and three-phase voltages to
the appropriate current and voltage terminals of the IED.
2. Inject current(s) and voltage(s) in a way that relevant measured (according to setting
parameter CurrentInput and VoltageInput) currents and voltages are created from
the test set.
Overall check in principal as above (non-directional overcurrent feature)
3. Trip value measurement
The relevant voltage restraining value (according to setting parameter
VoltageInput) has also to be injected from the test set and the influence on the trip
value has to be calculated when testing of the trip value is done.
4. Trip time measurement
Definite times may be tested as above (non-directional overcurrent feature). For
inverse time characteristics the PICKUP value (to which the overcurrent ratio has to
be calculated) is the actual pickup value as got with actual restraining from the
voltage restraining quantity.
11.8.1.4 Overcurrent feature with directionality
Please note that the directional characteristic can be set in two different ways either just
dependent on the angle between current and polarizing voltage (setting parameter
DirPrinc_OC1 or DirPrinc_OC2 set to or in a way that the trip value also is dependent on
the angle between current and polarizing voltage according to the I · cos(F) law (setting
parameter DirPrinc_OC1 or DirPrinc_OC2 set to I · cos(F). This has to be known if a
more detailed measurement of the directional characteristic is made, than the one
described below.
Procedure
1. Connect the test set for injection of three-phase currents and three-phase voltages to
the appropriate current and voltage terminals of the IED.
2. Inject current(s) and voltage(s) in a way that relevant measured (according to setting
parameter CurrentInput and VoltageInput) currents and voltages are created from
the test set.
3. Set the relevant measuring quantity current to lag or lead (lag for negative RCA
angle and lead for positive RCA angle) the relevant polarizing quantity voltage by
an angle equal to the set IED characteristic angle (rca-dir) when forward directional
feature is selected and the CTWYEpoint configuration parameter is set to ToObject.
If reverse directional feature is selected or CTWYEpoint configuration parameter is
set to FromObject, the angle between current and polarizing voltage shall be set
equal to rca-dir+180°.
Section 11 1MRK 504 165-UUS -
Testing functionality by secondary injection
228 Transformer protection RET670 2.2 ANSI
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals