EasyManua.ls Logo

ABB RET670 - Verifying Instantaneous Back-Up Trip at CB Faulty Condition

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The normal mode BuTripMode = 1 out of 3 should have been verified in the tests above.
In applicable cases the modes 1 out of 4 and 2 out of 4 can be checked. Choose the mode
below, which corresponds to the actual case.
Checking the case
BuTripMode
=
1 out of 4
It is assumed that the ground-fault current setting Pickup_N is below phase current setting
Pickup_PH.
1. Set BuTripMode = 1 out of 4.
2. Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase
current below set Pickup_PH but above Pickup_N . The residual ground-fault
should then be above set Pickup_N.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4. Disconnect AC and BFI_3P input signals.
Checking the case
BuTripMode
=
2 out of 4
The ground-fault current setting Pickup_N may be equal to or below phase-current setting
Pickup_PH.
1. Set BuTripMode = 2 out of 4.
2. Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase
current above set Pickup_PH and residual (ground fault) above set Pickup_N.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4. Apply the fault condition, including initiation of CCRBRF (50BF), with at least one-
phase current below set Pickup_PH and residual (ground fault) above set Pickup_N.
The current may be arranged by feeding three- (or two-) phase currents with equal
phase angle (I0-component) below Pickup_PH, but of such value that the residual
(ground fault) current (3I
0
) will be above set value Pickup_N.
5. Verify that back-up trip is not achieved.
6. Disconnect AC and BFI_3P input signals.
11.5.8.6 Verifying instantaneous back-up trip at CB faulty condition
Applies in a case where a signal from CB supervision function regarding CB being faulty
and unable to trip is connected to input 52FAIL.
Section 11 1MRK 504 165-UUS -
Testing functionality by secondary injection
194 Transformer protection RET670 2.2 ANSI
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Related product manuals