EasyManuals Logo

ABB RET670 Commissioning Manual

ABB RET670
328 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #286 background imageLoading...
Page #286 background image
10. Wait for a time corresponding to tDelayToAlarm1 from the appearance of
WARNING1 signal. Make sure that the ALARM1 signal appears.
11. Note the time taken for the appearance of ALARM1 signal from the appearance of
WARNING1 signal, and compare it with set value (tDelayToAlarm1).
12. Wait for a time corresponding to tDelayToAlarm2 from the appearance of
WARNING2 signal, and make sure that the ALARM2 signal appears.
13. Note the time taken for the appearance of ALARM2 signal from the appearance of
WARNING2 signal, and compare it with set value (tDelayToAlarm2).
14. Activate the BLKWRN binary input. The WARNING1 and WARNING2 signals
should disappear.
15. Activate the BLKALM binary input. The ALARM1 and ALARM2 signals should
disappear.
16. Reset the BLKWRN and BLKALM binary inputs. Once again warning and alarm
signals should appear.
17. Reduce the three-phase currents suddenly to value lower than the rated current and
take note of hot spot temperature.
18. Check the warnings reset limit (HystAbsHPT). Monitor the WARNING1 and
WARNING2 signals until they disappears on the corresponding binary outputs.
Take the HPTMPMAX readings and compare with the reset level settings.
Verifying LOLINDAY and LOLINYRS outputs
1. Connect the test set for injection of three-phase currents to the appropriate current
terminals of the IED.
2. Make sure that the settings in the IED are appropriate, especially set the EnaAgeCalc
setting as Enable, TimeToUpdate setting as 1 hour and AgeingRateMeth setting as
IEC.
3. Activate the TOTVALID input and set some temperature value in TOTEMP input.
4. Supply the IED with three-phase currents slightly more than the rated value.
5. Note the hot spot temperature (HPTMPMAX) and maintain it for another 1 hour.
6. Check the LOLINDAY and LOLINYRS outputs after 1 hour and compare it with the
calculated loss of life value using IEC standard method.
11.13.6.2 Completing the test
Continue to test another function or end the test by changing the Test mode setting to
Disabled. Restore connections and settings to their original values, if they were changed
for testing purposes.
Section 11 1MRK 504 165-UUS -
Testing functionality by secondary injection
280 Transformer protection RET670 2.2 ANSI
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals