11.4.14.1 Completing the test
Continue to test another function or end the test by changing the TESTMODE setting to
Disabled. Restore connections and settings to their original values, if they were changed
for testing purposes.
11.4.15 Under impedance protection for Generator ZGVPDIS
Prepare the IED for verification of settings.
Values of the logical signals for ZGVPDIS are available on the local HMI under Main
menu/Tests/Function status/Impedance/ZGVPDIS (21G, Z<)/
1:ZGVPDIS:ZGVPDIS. The Signal Monitoring in PCM600 shows the same signals that
are available on the local HMI.
11.4.15.1 Verifying the settings
Distance protection zones
While measuring operating characteristics, keep the current constant. Keep the current as
close as possible to its rated value or lower, however make sure it is higher than 30% of
the rated current.
If the measurement of the operating characteristics runs under constant voltage
conditions, ensure that the maximum continuous current in an IED does not exceed four
times its rated value.
To verify the zone 1 mho characteristic, at least two points must be tested.
1MRK 504 165-UUS - Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI 173
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals