Section 9 Establishing connection and verifying the
IEEE C37.118/1344 communication
9.1 Overview
The IED can support synchrophasor data communication via IEEE C37.118 and/or
IEEE1344 with maximum 8 TCP clients and 6 UDP client groups, simultaneously.
The rear OEM ports are used for IEEE C37.118/1344 communication. The same ports can
also be used for substation bus (IEC 61850-8-1) communication and process bus
(IEC/UCA 61850-9-2LE) communication where applicable.
In order to establish a connection between PMU and a TCP/UDP client (PDC client), an
Ethernet communication link (e.g. optical fiber) shall be available and the required
parameters on both PMU and the TCP/UDP client shall be set. For the purpose of this
section, an Open PDC tool (PMU Connection Tester) installed on a PC is used as the TCP/
UDP client.
9.2 Setting the PMU station communication (PMU Report)
1. Check the settings for the PMU Report parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Report/PMUREPORT:1
1.1. Make sure that the operation of at least one PMU instance (e.g. PMU1) is
Enabled.
1.2. Enable sending the frequency data by setting the parameter SendFreqInfo to
Enabled.
2. Check the operation of the required phasor channels (PHASORREPORT) by
navigating to: Main menu/Configuration/Communication/Station
communication/phasor measurement/PMU Report/PHASORREPORT:x.
1MRK 504 165-UUS - Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 2.2 ANSI 73
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals