1. Set AutoInitMode to DLD disabled and Mode to Impedance.
2. Activate the switch onto fault BC input.
During normal operating conditions, the BC input is de-energized.
3. Apply a three-phase fault condition corresponding to a fault at approximately 45%
of the line or with impedance at 50% of the used zone setting and current greater than
30% of IBase.
The ZACC input is activated.
4. Check that the TRIP output, external signals and indication are obtained.
11.4.13.2 Initiating ZCVPSOF automatically and setting mode to impedance
1. Set AutoInitMode to Voltage and Mode to Impedance.
2. Deactivate the switch onto fault BC input.
3. Set the current and voltage inputs to lower than IphPickup and UVPickup for at least
one second.
4. Apply a three-phase fault condition corresponding to a fault at approximately 45%
of the line or with impedance at 50% of the used zone setting and current greater than
30% of IBase.Apply a two-phase fault condition corresponding to a fault at
approximately 45% of the line or with impedance at 50% of the used zone setting and
current greater than 30% of IBase.
The ZACC input is activated.
5. Check that the correct TRIP output, external signals and indication are obtained.
11.4.13.3 Initiating ZCVPSOF automatically and setting mode to VILevel
1. Set AutoInitMode to Voltage and Mode to VILevel.
2. Deactivate the switch onto fault BC input.
3. Set the current and voltage inputs to lower than IphPickup and UVPickup for at least
one second.
4. Apply the three-phase currents in such a way that the magnitudes are greater than
IphPickup and the three-phase voltages in such a way that the magnitudes and lower
than UVPickup at least for the duration of the tDuration setting.
5. Check that the correct TRIP output, external signals and indication are obtained.
11.4.13.4 Completing the test
Continue to test another function or end the test by changing the TESTMODE setting to
Disabled. Restore connections and settings to their original values, if they were changed
for testing purposes.
1MRK 504 165-UUS - Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI 171
Commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals