IEC140000144 V1 EN
Figure 16: Captured synchrophasor data
9.5.2 Verifying the IEEE C37.118/1344 UDP communication
After setting both PMU configuration and the UDP client configuration (As explained in
sections
Setting the PMU station communication (PMU Report), Setting the PMU station
communication (PMU configuration) and Setting the TCP/UDP client communication)
and making sure that the Ethernet communication is set up, click Connect on the PMU
Connection Tester tool.
1MRK 504 165-UUS - Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 2.2 ANSI 85
Commissioning manual