User Manual MIC 900 / MIC 1100 / MIC 3000
38
Issue 17.08.2021_00
Enabling data logger: Under this code setting you can pre-program the data logger function:
„No“ = Data logger is inactive
Yes“ = Data logger is active
„Auto“ =Automatic logging of data: Processes are automatically logged on an SD card,
when VisuNet is not active.
Interval: Entering an interval time, how often you want to log data.
Factory setting: Data logger is switched off.
Interval = 000 min.
Hint
With an interval time of 0 min, data will be logged every 30 seconds.
If the data logger is active (Active = Yes), there can be a delay of up to 3 seconds at
the start of a program.
Hint
The data logger can only be used if VisuNet is enabled and a µSD card with enough
free memory has been inserted into the relevant slot.
If the option „Data logger“ is enabled, but there is not enough memory on the SD card, the
controller will realise this before the start of a program and it will show a corresponding
message on the display.
Data logger memory
If this message is acknowledged with „Nothe program start will be terminated.
If the message is acknowledged with „Yes” the data logger will temporarily be switched off and
the program will be started.
Be aware
Temporarily switched off means until the next reboot of the controller.
If there is not enough memory on the SD card, you can save the data from the SD card
onto a USB stick and free some memory (see "copy data onto USB stick ").
Be aware
When you want to use the Auto“ function, please make sure that there is an SD
card in the controller and that VisuNet is enabled. If there is no SD card in the
controller, the data cannot be logged by the controller. As soon as the controller is
connected to VisuNet, VisuNet will log the controller data.