1.2 System Power Requirements
Table 2 illustrates the current draw of each module at -48 V. Table 3 through Table 5
illustrate three different Total Access 3000/3010 arrangements with a current draw
of -48 V. Use Table 6 to determine wire gauge and fuse size. Use Table 8 to
calculate current draw for a single shelf deployment.
Table 2. Current Draw of Each Module At -48 V
Note: * The following equations are used for calculating T1-OR current draw and depend on span powering for
loop equipment and voltage input:
Nominal: (48 V/input voltage * (14.8 + span ohms / 10.16) + 45) mA
Maximum: (48 V/input voltage * (15 + span ohms / 10) + 50) mA
** x – Indicates feature list of card