EasyManua.ls Logo

AERMEC MULTI CONTROL - SYSTEM SETUP Procedures; Setting Remote Control

AERMEC MULTI CONTROL
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
4598010_00
GB
Setup menu
- SYSTEM SETUP procedures
The fi rst window of the SYSTEM SETUP allows the user to
set the type of remote control (if present) to be applied to
the MULTI CONTROL; this window displays the following
information:
- Type of remote control (
1
): indicates which type of
remote control is currently applied to the MULTI CONTROL
accessory.
From this window it is possible to:
(1) Set the type of remote control: pressing the key
C
will allow you to enter the modifi cation mode and the value
will be highlighted; by pressing the keys
A
or
B
it will
be possible to modify the value currently displayed, while
pressing the key
C
will confi rm this choice; the values that
can be set with this parameter are:
- BY VMF CRP 3 MODULE (indicates that remote control is
performed by the installed VMF CRP 3 accessory module;
for further information, see the installation section of the
components of the system in this manual).
- BY MODBUS SERIAL (indicates that the system is controlled by a
BMS supervision system; this system is implemented by using the
list of variables specifi ed on the following pages).
- NOT PRESENT (no remote control included).
(2) Pass on to the next window:
to go to the next window of this menu, press the key
B
.
(3) Exit this window:
press the key
A
to return to the selection of the SETUP menus.
(4) Exit this window:
press the key
D
to return to the selection of the USER menus.
• Setting remote control (Password 101 or 303):
A
B
C
ESC
D
Remote control
NOT
AVAIBLE
1
Remote control
NOT
AVAIBLE

Table of Contents