48
GB
4598010_00
101 R -200 700
1
/
10
°C Yes No No Water outlet temperature
102 R -200 700
1
/
10
°C Yes No No Water inlet temperature
103 -200 700
1
/
10
°C Yes No No External air temperature
104 -30 150
1
/
10
°C Yes No No Pressing gas temperature
105 -30 150
1
/
10
°C Yes No No Coil temperature
106 0 42 bar Yes No No High Pressure
107 0 42 bar Yes No No Low Pressure
108 0 150 Hertz or % Yes No No Inverter instant frequency/power
109 R -200 700
1
/
10
°C Yes No No Instant control setting
110 R 0 6 // Yes No No
Unit status (0:OFF, 1:STAND_BY, 2:PUMP_ON,
3:COMPRESSOR_ON, 4:DEFROSTING, 5: NOT
CONNECTED, 6: ALARM PRESENCE)
111 R 0 1 // Yes No No Unit season (0:cooling, 1:heating)
112 R 0 255 // Yes No No Alarm code
113 R -200 700
1
/
10
°C Yes No No Water outlet temperature
114 R -200 700
1
/
10
°C Yes No No Water inlet temperature
115 -200 700
1
/
10
°C Yes No No External air temperature
116 -30 150
1
/
10
°C Yes No No Pressing gas temperature
117 -30 150
1
/
10
°C Yes No No Coil temperature
118 0 42 bar Yes No No High Pressure
119 0 42 bar Yes No No Low Pressure
120 0 150 Hertz or % Yes No No Inverter instant frequency/power
121 R -200 700
1
/
10
°C Yes No No Instant control setting
122 R 0 6 // Yes No No
Unit status (0:OFF, 1:STAND_BY, 2:PUMP_ON,
3:COMPRESSOR_ON, 4:DEFROSTING, 5: NOT
CONNECTED, 6: ALARM PRESENCE)
123 R 0 1 // Yes No No Unit season (0:cooling, 1:heating)
124 R 0 255 // Yes No No Alarm code
125 R -200 700
1
/
10
°C Yes No No Water outlet temperature
126 R -200 700
1
/
10
°C Yes No No Water inlet temperature
127 -200 700
1
/
10
°C Yes No No External air temperature
128 -30 150
1
/
10
°C Yes No No Pressing gas temperature
129 -30 150
1
/
10
°C Yes No No Coil temperature
130 0 42 bar Yes No No High Pressure
131 0 42 bar Yes No No Low Pressure
132 0 150 Hertz or % Yes No No Inverter instant frequency/power
133 R -200 700
1
/
10
°C Yes No No Instant control setting
134 R 0 6 // Yes No No
Unit status (0:OFF, 1:STAND_BY, 2:PUMP_ON,
3:COMPRESSOR_ON, 4:DEFROSTING, 5: NOT
CONNECTED, 6: ALARM PRESENCE)
135 R 0 1 // Yes No No Unit season (0:cooling, 1:heating)
136 R 0 255 // Yes No No Alarm code
137 R -200 700
1
/
10
°C Yes No No Water outlet temperature
138 R -200 700
1
/
10
°C Yes No No Water inlet temperature
139 -200 700
1
/
10
°C Yes No No External air temperature
140 -30 150
1
/
10
°C Yes No No Pressing gas temperature
141 -30 150
1
/
10
°C Yes No No Coil temperature
142 0 42 bar Yes No No High Pressure
143 0 42 bar Yes No No Low Pressure
144 0 150 Hertz or % Yes No No Inverter instant frequency/power
145 R -200 700
1
/
10
°C Yes No No Instant control setting