Clear the Alarm History
At significant points such as during preventative maintenance and after commissioning, it may be desired
to clear the alarm history.
Warning. Alarm history is collected because it can be very helpful in identifying a problem with the
system. The alarm history should never be arbitrarily cleared by an operator. Only AAST should
clear the alarm history after all the alarms stored in history have been recorded.
To clear the alarm history, perform the following steps:
1. Hold the Esc button until the main screen is displayed.
2. Press Prg and enter the password (0004). Press Enter.
3. Press Down until the cursor is over “System” and press Enter.
4. Press Down until the cursor is over “Initialization” and press Enter.
5. Press Down until the cursor is over “Delete Alarm Logs” and press Enter.
6. Press Up or Down until the “no” becomes “yes” and press Enter.
Enable SNMP (Optional)
SNMP is available on the ASMUC as an optional extra. To enable it, perform the following steps:
1. Hold the Esc button until the main screen is displayed.
2. Press Prg and enter the password (0004). Press Enter.
3. Press Down until the cursor is over “System” and press Enter.
4. Press Down until the cursor is over “Serial Ports” and press Enter.
5. Press Down until “SNMP Recipients Config” is displayed across the top.
6. Press Enter until the cursor is next to “SNMP” and use the Up or Down buttons to change “No”
to “YES”.
7. Press Enter to confirm.
8. Press Enter until the cursor is over the IP address fields.
9. Use the Up and Down buttons to change the value of each part of the IP address. When finished,
press Enter to move to the next part of the IP address.
10. To add additional recipients, press Enter until the cursor is in the upper left corner and press
Down to access the IP settings for the other recipients.
11. Repeat steps 7-10 as needed. Up to 5 recipients can be added.