Control Configuration Menu Parameters
NOTE: This menu contains options for the network, setpoints, free cooling, sensors, and input/output
logic.
Table 25: Parameters in the Network Menu
Menu Screen
Option
Description
Default
Net Config
Total HVACs
Number of HVAC Units
2
Total Zones
Number of Control Zones
1
En Zone Temp Sensor
Enable Zone Temp Sensors
No
Network View
Unit ID
Select Unit to View IP Address
1
View
View Unit IP Address
--
Network
Configuration
Unit ID
Select Unit to Change IP Address
1
New
Change Unit IP Address
--
Network Config
Assign units to each zone and configure operating mode
HVAC Model Setting
Unit ID
Select model of each HVAC Unit
--
Table 26: Parameters in the Setpoints Menu
Menu Screen
Option
Description
Default
Zone Configuration
Backup Number
Number of Backup Units in Zone
0
Setpoint
Zone Setpoint
79°F
Dead Zone
Zone Deadband
1.8°F
Comfort Set
Zone Comfort Mode Setpoint
72°F
Dehum Number
Number of Units in Dehumidification
1
Room Temperature
Cool Band
PID controller dead band
1.8°F
Cool Diff
Allowed temperature range for compressor
operation
F
Cool Dead
Temperature range around setpoint for
compressor operation
F
Backup Diff
Temperature differential above setpoint at which
the backup units will come on
F
Backup Offset
Temperature offset at which the backup units
will shut off
F
Room Temperature
PID
Kp
Proportional control setting
25
Ti
Integral control setting
120
Td
Derivative control setting
0
Comfort
Temperature
Setpoint
Comfort mode setpoint
72°F
Keep Time
Comfort mode duration
60 min
Heater
Heater Turn On Diff
Temperature range for heater operation
F
Heater Deadband
Temperature below setpoint at which heater
turns on
29°F
Dehumidification
Enable
Enable Dehumidification
Disable
Setpoint
Humidity setpoint
55%
Diff
Humidity level above setpoint at which
dehumidification starts
15%