Figure 36 : Heater Operation Logic
Dehumidification
Dehumidification using the compressor or heater is available using the compressor or heater. It can be
enabled under “Setpoints” in the Control Configuration menu. When the humidity reading from the
controller exceeds a threshold (default 15% above target), dehumidification will activate. The heater will
activate if the indoor temperature is below a certain level (default 11°F below setpoint). Otherwise, the
compressor will be used to dehumidify. Dehumidification will stay active until the target is reached
(default 55%).
Figure 37: Dehumidification Logic