Alarm delay
Delay before alarm triggers
12 min
Low Temp
Low Temp Alarm Diff
Low room temperature alarm trigger point
34°F
Delay time
Delay before alarm triggers
60s
High Temp
High Temp Alarm Diff
High room temperature alarm trigger point.
Alarm will trigger if temperature is this much
higher than the setpoint
16°F
Delay time
Delay before alarm triggers
60s
Low Supply temp
Low supply temp
Low supply temperature alarm trigger point
10.8°F
Delay time
Delay before alarm triggers
20s
Dirty Condenser
Enable Dirty
Condenser
Enable dirty condenser alarm
Yes
Subcool Setpoint
Maximum allowed supercool before triggering
alarm
41°F
Subcool Diff
Temperature above supercool setpoint at which
the alarm will restore
5.8°F
Threshold Set
Subcool threshold
80%
Generator run
FC limited by Gen.
Disable free cooling during generator run
No
Comp limited by Gen.
Compressor speed limited by generator run
Yes