Contact: AIRSYS North America Phone: (855) 874-5380 Page 47 of 112
Email: ASNSupport@air-sys.com Web: http://airsysnorthamerica.com Rev 1.15
Site name or building serial #: ______________
ASMUC.6 Serial #: ______________________
Date Tested: ____________________________
Name of Tester: ______________________
Title/Position: ________________________ Contact
information: e. _________________
Ph. _________________
1. Change System Units (Optional)
2. Set the Unit Model
3. Set the Unit Numbers
4. Turn ON the HVAC System
5. Execute Step Test (verifies all functions of each WPU)
5.1. HVAC Supply Fans
5.2. HVAC Heaters
5.3. HVAC Condenser Fans
5.4. HVAC Mechanical Cooling
5.5. HVAC Outside Air Damper
6. Set the System Clock
7. Verify Temp and Humidity sensor readings and Setpoint
7.1. Primary Indoor Temp sensor
7.2. Humidity sensor
7.3. External (outside) Temp sensor
7.4. Confirm indoor temperature setpoint
8. Verify Signal from Generator
9. Verify Smoke/Fire Alarm
10. Verify HVAC Alarms
11. Verify DC-Failover
(if installed)
12. Clear Alarm History
(Optional)
13. Fill out Warranty Card and send to AIRSYS North America