Table 28: Parameters in the Sensors Menu
Note: Parameters in gray can only be accessed by connecting a PGD to the unit or via the html interface.
Menu Screen
Option
Description
Default
Sensor Settings
Humidity Min Value
Minimum allowed humidity value
20%
Humidity Max Value
Maximum allowed humidity value
150%
Sensor Settings
(Unit Only)
HP min. value
Minimum allowed high pressure sensor value
0 psi
HP max. value
Maximum allowed high pressure sensor value
652.7 psi
LP min. value
Minimum allowed low pressure sensor value
14.5 psi
LP max. value
Maximum allowed low pressure sensor value
514.9 psi
Sensor Offset
Outdoor temp
Outdoor temperature sensor offset
F
Room temp
Room temperature sensor offset
F
Outdoor hum
Outdoor humidity sensor offset
0%
Sensor Offset (Unit
Only)
Supply temp
Supply temperature offset
F
Room temp
Room temperature sensor offset
F
Outdoor temp
Outdoor temperature sensor offset
F
Dscg temp
Compressor discharge temperature sensor offset
F
Suct. press
Suction pressure sensor offset
0 psi
Cond. press
Condensing pressure sensor offset
0 psi
Suct. temp
Suction temperature sensor offset
F
Cond. temp
Condensing temperature sensor offset
F
Filter air pressure
Filter air pressure sensor offset
0 psi
Table 29: Parameters in the I/O Logic Menu
Menu Screen
Option
Description
Default
Component Logic
Exhaust Damper
Exhaust Damper Alarm Logic
N.O
Component Output
logic (unit only)
Comp
Compressor alarm output logic
N.O